WONDER — The Mystery
Changing Flux Couples Separate Windings
Two separate windings can exchange energy through changing magnetic flux without mechanical rotation. A conventional transformer uses magnetic coupling, often improved by a ferromagnetic core. Voltage ratio follows turns in the ideal model; source power still has to supply the load.
Model: For ideal windings sharing the same changing flux, matched terminal voltage ratio is Vs/Vp = Ns/Np. With input and output currents defined into the primary and out of the secondary dotted terminals, Ip = (Ns/Np) Is in the ideal load model. Voltage ratio and current ratio compare the two sides of one operating condition; they do not impose a fixed output current when the load or turns ratio changes.
PREDICT — Commit to Your Answer
DOK 2 — PredictAn ideal transformer has 100 primary turns and 200 secondary turns. Its sinusoidal input is 10 V RMS. What is the open-circuit secondary RMS voltage?
Commit to both a prediction and a reason before revealing the explanation.
Step 1: Pick your answer.
STOP! Before revealing — why did you pick that?
Correct prediction and reasoning saved.
The ideal voltage ratio is 200/100 = 2. The secondary is 20 V RMS. Open circuit carries no load current in the ideal model.
▶ PLAY — An Ideal Transformer Under a Defined Load
DOK 2 — InvestigatePredict, measure and compare
Compare two input RMS voltages at the same turns and load, then two secondary turn counts at the same input and load. Watch current reversal and changing core field. Test zero input.
Ideal steady sinusoidal transformer: Np = 100, frequency 50 Hz, perfect coupling, infinite core permeability, no winding/core loss or magnetizing current. Controls set primary RMS voltage Vp, secondary turns Ns and pure secondary load R. Matched dotted terminal voltages are vp = √2 Vp sinωt and vs = (Ns/Np)vp. Zero-offset common flux is Φ = −√2 Vp cosωt/(Npω), so vp = Np dΦ/dt. Load current is is = vs/R, and source current ip = (Ns/Np)is. Instantaneous input and output powers are equal. A 0.020 s physical cycle plays over 6 real seconds. Moving conventional-current markers have schematic path speed proportional to current; they are not measured carrier drift. Core arrows show field direction and reverse with flux; field lines are not moving material. At fixed R, increasing turns ratio increases both secondary current and power demand on the ideal source. Steady DC operation is outside this periodic model.
Status: Ready
Playback: 6 real seconds per run; read elapsed physical model time. Pause or Step for measurements.
Measurements
Load givens — then predict and run
Loading a setup earns no trial credit.
♢ DISCOVER — Turns, Current and Load Conditions
DOK 1 — RecallFlip all 4 rule cards. Keep the quantities and model conditions clear.
Rule 1
Ideal voltage ratio
Click to flip
Ideal voltage ratio
Perfectly linked turns have equal voltage per turn. Vs/Vp = Ns/Np applies consistently to corresponding instantaneous values, amplitudes or RMS values. Matched terminal polarity follows winding orientation; changing dots can reverse secondary phase.
Rule 2
Current and power
Click to flip
Current and power
For the lossless ideal transformer with negligible magnetizing current, input power equals output power. Source current and delivered load current have inverse side-to-side turns ratios. General AC real power includes phase; VpIp = VsIs as real RMS power here assumes a purely resistive load.
Rule 3
A fixed load can draw more
Click to flip
A fixed load can draw more
Increasing Ns at fixed Vp, Np and R increases Vs and Is, so output power rises and the source supplies more input current. Saying “voltage rises so current halves” is valid for the two sides at equal transferred power, not a universal across-experiment rule.
Rule 4
Core, coupling and isolation
Click to flip
Core, coupling and isolation
A high-permeability core improves coupling; air-core transformers also exist. Thin electrically insulated laminations suppress eddy-current loops, while suitable ferrites suit other frequency ranges. Separate windings can provide galvanic isolation; equal turns alone do not guarantee isolation, and isolation does not make every contact safe.
All rules explored.
MISCONCEPTION ATTACK — Destroy the Myths
DOK 2 — AnalyzeChoose TRUE or FALSE for each claim. The explanation appears after an attempt; only a correct answer completes the claim.
Myth 1: “A step-up transformer creates extra energy because its voltage is higher.”
Correct — the claim is false.
False. Its source must supply the delivered energy. Equal ideal input/output power does not mean input power is fixed when a load changes.
Myth 2: “Equal primary and secondary turns automatically guarantee electrical isolation.”
Correct — the claim is false.
False. Isolation comes from separately insulated windings. An autotransformer can share a conducting winding; turns ratio alone is insufficient.
Both myths corrected. Continue to the instructor questions.
✦ THE SECOND “AHA!” — Ideal Ratios and Changing Flux
DOK 2 — ApplyUse a sinusoidal input and explicitly stated ideal assumptions.
Instructor Q1 — Sustained Induction
Which is essential for continuous transformer e.m.f.?
Instructor Q2 — Fixed Secondary Resistor
Double secondary RMS voltage across the same pure R. Its RMS current:
Instructor Q3 — Step-Down Voltage
Ideal separate windings have Np = 300, Ns = 75 and primary RMS voltage 20 V. Find secondary RMS voltage.
Instructor Q4 — Side-to-Side Current
An ideal transformer has Ns/Np = 3 and supplies a resistive load with secondary RMS current 0.20 A. Find primary RMS current.
4/4 — Instructor Questions Completed
Specify the load and what is held constant before describing how a step-up changes current or power.
✎ PRACTICE — Independent Transformer Load Audits
DOK 1–3 — PracticeChallenge 1: Ideal Output Voltage
An ideal transformer has Np = 120, Ns = 30 and sinusoidal primary voltage 16 V RMS. Find secondary RMS voltage.
Step-by-Step Solution
Vs = 16×30/120 = 4.0 V RMS.
Challenge 2: Defined Resistive Load
An ideal transformer has Np = 400, Ns = 100 and sinusoidal primary voltage 24 V RMS. Its secondary supplies a pure 12 Ω resistor. Find secondary RMS voltage, secondary RMS current and primary RMS current.
Step-by-Step Solution
Vs = 24×100/400 = 6.0 V; Is = 6/12 = .50 A; output power = 3.0 W, so Ip = 3/24 = .125 A.
Challenge 3: Audit a Fixed-Load Step-Up
An ideal transformer has Np = 100 and 10 V RMS sinusoidal input. A pure 10 Ω resistor is connected to its secondary. Secondary turns change from 100 to 200 while input voltage and R stay fixed. Find the new primary RMS current and output mean power. A report says the secondary current must halve, the higher power is free energy from the core, and directly applying constant DC voltage gives the same continuing ideal operation. Correct all three claims and explain the required flux change.
Explanation checks are indicative. Compare your reasoning with the worked solution or your teacher.
Step-by-Step Solution
New Vs = 20 V, Is = 20/10 = 2.0 A; output power = 40 W; Ip = 40/10 = 4.0 A. Secondary current doubles at fixed R; the source supplies the increased power. A practical transformer connected directly to constant DC voltage can develop rising magnetizing current, saturation and heating; once its flux is steady there is no continuous secondary e.m.f. The ideal periodic model does not describe this DC transient. Changing linked flux is essential.
☷ CHALLENGE — Transformer Conditions
DOK 2 — ApplyTransformer Conditions
Select each statement and place it in its matching category. Judge the physical conditions.
0 / 6 correct
Physics Insight
Specify the load and what is held constant before describing how a step-up changes current or power.
TEACH — The Feynman Technique
DOK 3 — TeachYour Final Mission: Explain common changing flux, matched winding voltages, current ratios, fixed-load changes, ideal versus real behaviour and why direct steady DC is not ordinary periodic transformer operation.
Use simple words and at least three short sentences. This checks effort; compare your physics with the Vault or your teacher.
Type Your Explanation (≥ 3 sentences)
Draw a labelled explanation with at least three purposeful strokes. This checks effort; compare your physics with the Vault or your teacher.
Cyan pen selected.
Final reward below
Hidden exam secrets inside — Crest's private notebook.
Crest’s Secret Notebook
Mission 11.17 — Transformers
Reach the Peak of Understanding
1. Ideal voltage ratio
Perfectly linked turns have equal voltage per turn. Vs/Vp = Ns/Np applies consistently to corresponding instantaneous values, amplitudes or RMS values. Matched terminal polarity follows winding orientation; changing dots can reverse secondary phase.
2. Current and power
For the lossless ideal transformer with negligible magnetizing current, input power equals output power. Source current and delivered load current have inverse side-to-side turns ratios. General AC real power includes phase; VpIp = VsIs as real RMS power here assumes a purely resistive load.
3. A fixed load can draw more
Increasing Ns at fixed Vp, Np and R increases Vs and Is, so output power rises and the source supplies more input current. Saying “voltage rises so current halves” is valid for the two sides at equal transferred power, not a universal across-experiment rule.
4. Core, coupling and isolation
A high-permeability core improves coupling; air-core transformers also exist. Thin electrically insulated laminations suppress eddy-current loops, while suitable ferrites suit other frequency ranges. Separate windings can provide galvanic isolation; equal turns alone do not guarantee isolation, and isolation does not make every contact safe.
5. Flux and voltage phase
For the chosen terminal convention v = N dΦ/dt. A sine terminal voltage corresponds to a negative-cosine zero-offset flux. Load current follows voltage for a pure resistor, not flux. Real magnetizing current also depends on permeability, hysteresis and saturation.
6. Switched supplies and losses
A steady primary current gives steady flux and no continuous secondary induction. Switched or alternating excitation can produce changing flux. Practical isolated converters can use high-frequency transformers plus electronics; DC conversion is not restricted to directly connecting a battery to a conventional winding.
Worked independent practice
C1: 4.0 V RMS. C2: 6.0 V, 0.50 A and 0.125 A. C3: new input current 4.0 A and output mean power 40 W; the source supplies the increase.
Live investigation and access
Ideal steady sinusoidal transformer: Np = 100, frequency 50 Hz, perfect coupling, infinite core permeability, no winding/core loss or magnetizing current. Controls set primary RMS voltage Vp, secondary turns Ns and pure secondary load R. Matched dotted terminal voltages are vp = √2 Vp sinωt and vs = (Ns/Np)vp. Zero-offset common flux is Φ = −√2 Vp cosωt/(Npω), so vp = Np dΦ/dt. Load current is is = vs/R, and source current ip = (Ns/Np)is. Instantaneous input and output powers are equal. A 0.020 s physical cycle plays over 6 real seconds. Moving conventional-current markers have schematic path speed proportional to current; they are not measured carrier drift. Core arrows show field direction and reverse with flux; field lines are not moving material. At fixed R, increasing turns ratio increases both secondary current and power demand on the ideal source. Steady DC operation is outside this periodic model.
Run, Pause, Step and Reset work offline. Complete three matched measurements. Loading a preset is not completing a trial. Saved progress resumes paused. Reduced-motion Run gives a final snapshot; Step allows deliberate inspection. Hints and solutions require a genuine unsuccessful numerical attempt and never complete a task. Explanation rubrics are indicative; compare your physics with the solution or a teacher. Teaching submission checks effort rather than certifying scientific accuracy.
Course scope
Transformers are declared enrichment applications of electromagnetic induction. They are not claimed as separately listed required topics in the current A Level 9702 or AP Physics 2 frameworks. The common-flux sinusoidal ideal model is an extension with explicit assumptions.
Sources: Cambridge International 9702 syllabus ; College Board AP Physics 2 CED. Detailed extension models are labelled in the mission.
✓ Crest’s Checklist
- I specify RMS or instantaneous values.
- I specify load and fixed parameters.
- I compare current ratios consistently.
- I distinguish changing flux from steady current.
- I distinguish turns ratio from galvanic isolation.
— Crest ☆ “Reach the Peak of Understanding”
Mission 11.17 Complete! · All 10 levels cleared · PHYSICS CREST
★ Transformers Investigator
Specify the load and what is held constant before describing how a step-up changes current or power.