WONDER — The Mystery
Power Transfer and Line Heating
A transmission line is part of a complete circuit. Its resistance transfers electrical energy to thermal energy. Raising voltage can reduce current and heating for a specified transferred power, but the load, sending power and voltage drop must be stated consistently.
Model: In the declared steady DC two-wire model, sending voltage Vs and sending power Ps fix current I = Ps/Vs. R is the total resistance of both conductors. Receiving voltage is Vr = Vs − IR, line heating is I²R, and receiving power is Pr = Ps − I²R. An adjusted resistive load draws the stated current; its value is Vr/I. Holding sending power fixed does not hold receiving power fixed.
PREDICT — Commit to Your Answer
DOK 2 — PredictA steady line carries 5 A. Its total outgoing-plus-return resistance is 4 Ω. Current becomes 2.5 A with the same line resistance. What happens to line heating power?
Commit to both a prediction and a reason before revealing the explanation.
Step 1: Pick your answer.
STOP! Before revealing — why did you pick that?
Correct prediction and reasoning saved.
The loss changes from 5²×4 = 100 W to 2.5²×4 = 25 W.
▶ PLAY — Complete Circuit: Power and Energy Balance
DOK 2 — InvestigatePredict, measure and compare
Compare sending voltage at fixed sending power and line resistance, then compare line resistance at fixed voltage and sending power. Measure source, line and load energy over 10 s. Test zero power.
Steady DC two-wire model, not a three-phase AC grid. Sending voltage Vs and sending power Ps are controlled; R is total conductor resistance. I = Ps/Vs, Vr = Vs − IR, Ploss = I²R and Pr = Ps − Ploss. The receiving resistance is adjusted to Vr/I at each operating condition; no fixed-load claim is made. Control limits guarantee Vr > 0 when Ps > 0. Source, heat and load energies are Ps t, Ploss t and Pr t; transient propagation and temperature are not modeled. Ten physical seconds play over six real seconds. Conventional-current markers circulate around the complete circuit with schematic speed proportional to I; these are not energy packets or measured electron drift. Heat-bar growth shows accumulated thermal energy, not measured temperature. All current stops for zero sending power.
Status: Ready
Playback: 6 real seconds per run; read elapsed physical model time. Pause or Step for measurements.
Measurements
Load givens — then predict and run
Loading a setup earns no trial credit.
♢ DISCOVER — Specify the Complete Power Balance
DOK 1 — RecallFlip all 4 rule cards. Keep the quantities and model conditions clear.
Rule 1
Two conductors and a voltage drop
Click to flip
Two conductors and a voltage drop
Use total loop resistance, including outgoing and return conductors. For a steady DC resistive model Vs − Vr = IR. The load receives Vr, not automatically the sending voltage.
Rule 2
Current squared heating
Click to flip
Current squared heating
Line heating power is I²R. Here I is steady DC current. With sinusoidal AC resistance, average heating uses RMS current; real grids also have reactance, phase, capacitance and multiple conductors.
Rule 3
What stays fixed matters
Click to flip
What stays fixed matters
At fixed sending power Ps and voltage Vs, I = Ps/Vs. Increasing Vs at fixed Ps and R reduces loss. Receiving power then increases by the saved heating; it is not held fixed. A fixed resistor would give a different current comparison.
Rule 4
A grid is more than this model
Click to flip
A grid is more than this model
Conventional transformers make AC voltage changes convenient; switched electronics and HVDC conversion also exist. Actual voltage stages and end-use voltages vary by network. High voltage requires insulation, clearances and protection; it is not chosen because it is intrinsically safer.
All rules explored.
MISCONCEPTION ATTACK — Destroy the Myths
DOK 2 — AnalyzeChoose TRUE or FALSE for each claim. The explanation appears after an attempt; only a correct answer completes the claim.
Myth 1: “Higher transmission voltage is intrinsically safer.”
Correct — the claim is false.
False. For fixed transferred power it can reduce current and conductor heating, but high voltage creates serious insulation and clearance requirements.
Myth 2: “Transformers create the energy saved by high-voltage transmission.”
Correct — the claim is false.
False. They allow voltage conversion; reducing line heating leaves more of the source energy available to the load. Real transformers and converters also have losses.
Both myths corrected. Continue to the instructor questions.
✦ THE SECOND “AHA!” — Voltage Drop and Heating
DOK 2 — ApplyEvery numerical item declares steady DC current or a complete sending condition.
Instructor Q1 — Total Line Resistance
A two-wire line has 2 Ω in each conductor. Which resistance belongs in the total heating calculation?
Instructor Q2 — Fixed Sending Power
Double sending voltage with sending power and total R fixed. The line current:
Instructor Q3 — Conductor Heating
A steady 6 A flows through a complete line with total resistance 3 Ω. Find total conductor heating power.
Instructor Q4 — Receiving Voltage
A sending source is 1200 V DC. Line current is 8 A and total conductor resistance is 5 Ω. Find receiving voltage.
4/4 — Instructor Questions Completed
Compare energy at the sending end, along both conductors and at the receiving load before claiming an efficiency improvement.
✎ PRACTICE — Independent Transmission Audits
DOK 1–3 — PracticeChallenge 1: Line Heating
A complete two-wire line carries steady current 3.0 A and has total resistance 8.0 Ω. Find the total heating power in its conductors.
Step-by-Step Solution
Ploss = 3.0²×8.0 = 72 W.
Challenge 2: Sending and Receiving
A line receives 24 kW from a 3000 V DC source. Its total conductor resistance is 6 Ω and its load is adjusted to this operating condition. Find steady current, receiving power and line thermal energy in 20 s.
Step-by-Step Solution
I = 24000/3000 = 8.0 A; loss = 8²×6 = 384 W; receiving power = 23616 W; thermal energy = 384×20 = 7680 J.
Challenge 3: Choose a Feasible Operating Condition
A complete DC line has total conductor resistance 10 Ω. Sending power stays at 50 kW with an adjusted resistive receiving load. Compare sending voltages 1000 V and 5000 V. A plan requires at least 45 kW at the receiving end and at most 2 kW conductor heating. Choose the feasible voltage, calculate its receiving voltage and receiving power, and explain why fixed sending power is different from fixed receiving power. State one limitation when applying this model to an actual AC grid.
Explanation checks are indicative. Compare your reasoning with the worked solution or your teacher.
Step-by-Step Solution
1000 V gives I = 50 A, loss = 25 kW and receiving power = 25 kW: both requirements fail. 5000 V gives I = 10 A, loss = 1 kW, Vr = 4900 V and Pr = 49 kW: both pass. Sending power is fixed but receiving power increases when line loss decreases; the load is adjusted. An actual AC grid requires RMS quantities, phase/reactance and often three-phase analysis.
☷ CHALLENGE — One Illustrative AC Supply Path
DOK 2 — ApplyOne Illustrative AC Supply Path
Select each statement and place it in its matching category. Judge the physical conditions.
0 / 6 correct
Physics Insight
This is an illustrative AC path. Actual stage counts and voltages vary; HVDC routes can include converter stations.
TEACH — The Feynman Technique
DOK 3 — TeachYour Final Mission: Explain total conductor resistance, voltage drop, sending versus receiving power, current-squared heating, energy balance and limits of a simplified DC line.
Use simple words and at least three short sentences. This checks effort; compare your physics with the Vault or your teacher.
Type Your Explanation (≥ 3 sentences)
Draw a labelled explanation with at least three purposeful strokes. This checks effort; compare your physics with the Vault or your teacher.
Cyan pen selected.
Final reward below
Hidden exam secrets inside — Crest's private notebook.
Crest’s Secret Notebook
Mission 11.18 — Power Transmission
Reach the Peak of Understanding
1. Two conductors and a voltage drop
Use total loop resistance, including outgoing and return conductors. For a steady DC resistive model Vs − Vr = IR. The load receives Vr, not automatically the sending voltage.
2. Current squared heating
Line heating power is I²R. Here I is steady DC current. With sinusoidal AC resistance, average heating uses RMS current; real grids also have reactance, phase, capacitance and multiple conductors.
3. What stays fixed matters
At fixed sending power Ps and voltage Vs, I = Ps/Vs. Increasing Vs at fixed Ps and R reduces loss. Receiving power then increases by the saved heating; it is not held fixed. A fixed resistor would give a different current comparison.
4. A grid is more than this model
Conventional transformers make AC voltage changes convenient; switched electronics and HVDC conversion also exist. Actual voltage stages and end-use voltages vary by network. High voltage requires insulation, clearances and protection; it is not chosen because it is intrinsically safer.
5. HVDC and real engineering
HVDC is useful for selected long-distance, submarine and interconnection applications, with converter costs and losses. It is not universally more efficient than every AC route. Selection depends on distance, power, topology and design.
6. Avoid impossible low-voltage examples
If I²R exceeds stated sending power, a positive passive receiving load cannot operate under those assumptions. Check receiving voltage and power instead of silently clamping a negative answer to zero.
Worked independent practice
C1: 72 W. C2: 8.0 A, 23616 W and 7680 J. C3: 5000 V sending, 4900 V receiving and 49 kW delivered; the lower-voltage candidate fails both requirements.
Live investigation and access
Steady DC two-wire model, not a three-phase AC grid. Sending voltage Vs and sending power Ps are controlled; R is total conductor resistance. I = Ps/Vs, Vr = Vs − IR, Ploss = I²R and Pr = Ps − Ploss. The receiving resistance is adjusted to Vr/I at each operating condition; no fixed-load claim is made. Control limits guarantee Vr > 0 when Ps > 0. Source, heat and load energies are Ps t, Ploss t and Pr t; transient propagation and temperature are not modeled. Ten physical seconds play over six real seconds. Conventional-current markers circulate around the complete circuit with schematic speed proportional to I; these are not energy packets or measured electron drift. Heat-bar growth shows accumulated thermal energy, not measured temperature. All current stops for zero sending power.
Run, Pause, Step and Reset work offline. Complete three matched measurements. Loading a preset is not completing a trial. Saved progress resumes paused. Reduced-motion Run gives a final snapshot; Step allows deliberate inspection. Hints and solutions require a genuine unsuccessful numerical attempt and never complete a task. Explanation rubrics are indicative; compare your physics with the solution or a teacher. Teaching submission checks effort rather than certifying scientific accuracy.
Course scope
Power transmission is declared circuit/induction application enrichment, not a separately listed required topic in the current A Level 9702 or AP Physics 2 frameworks.
Sources: Cambridge International 9702 syllabus ; College Board AP Physics 2 CED. Detailed extension models are labelled in the mission.
✓ Crest’s Checklist
- I include the return conductor.
- I specify which power stays fixed.
- I use receiving voltage at the load.
- I conserve source, heat and load energy.
- I qualify the DC model before applying it to an AC grid.
— Crest ☆ “Reach the Peak of Understanding”
Mission 11.18 Complete! · All 10 levels cleared · PHYSICS CREST
★ Power Transmission Investigator
Compare energy at the sending end, along both conductors and at the receiving load before claiming an efficiency improvement.